Reflectometry-based insulation moisture/leak and corrosion detection system.
Publish Time: Author: Site Editor Visit: 12
Reflectometry-based insulation moisture/leak and corrosion detection system
System concept
- Insulation humidity / leak detection: Reflectometry analysis is used to detect and localize moisture ingress or leakage within an insulation layer.
- Impedance measurement / TDR: Time Domain Reflectometry (TDR) measures impedance discontinuities along the sensing line to locate faults and estimate their position.
- Embedded sensing wire: A 1.5 mm² bare tinned-copper wire or 1.5 mm² copper wire is integrated into the insulation. A spacer presses the copper wire against or into the insulation layer to provide consistent electrical coupling.
- Drainage: PPS (polyphenylene sulfide) drain plugs can provide controlled drainage paths while maintaining the required mechanical and environmental resistance.
- Multi-state corrosion sensing: The system can incorporate corrosion-sensor elements representing different surface conditions, for example:
- bare steel
- painted/coated steel
- other protected or unprotected metal states
- Analysis: Changes in impedance, dielectric properties, and reflectometry response can be analyzed to distinguish dry insulation, localized humidity, water ingress, insulation damage, and corrosion-related changes.
A key point is that TDR primarily localizes impedance discontinuities; humidity localization depends on how moisture changes the electrical properties of the sensing structure. The sensor geometry, wire-to-insulation coupling, dielectric constant, and calibration therefore strongly affect the achievable localization accuracy.